LUTRON QSE-CI-WCI WALL BOX CONTACT CLOSER INTERFACE

LUT-QSE-CI-WCI

The QSE-CI-WCI from Lutron is a control interface for use with HomeWorks QS systems and QS standalone applications. The QSE-CI-WCI integrates a contact closure keypad with a Lutron lighting control system.

The QSE-CI-WCI from Lutron is a control interface for use with HomeWorks QS systems and QS standalone applications. It integrates a contact closure keypad with a Lutron lighting control system. The WCI provides up to eight contact closure inputs (CCIs), which accept maintained or momentary signals.

This CCIs are programmable through the HomeWorks QS system setup software, which means the CCI can be set up to simulate existing Lutron® keypad functionality or custom configured to meet project specific requirements

For QS standalone applications, the CCIs are programmable using the button, DIP switch and LEDs on the WCI.


FEATURES

  • Provides 8 contact closure inputs (CCIs), maintained or momentary
  • Works with SELV/PELV/NEC® Class 2, low voltage dry contact closures
  • The CCI can be set up to simulate existing Lutron® keypad functionality or custom configured to meet project specific requirements
  • Place in the wall box behind a contact closure keypad
  • Provides a 1 way interface between the Lutron® lighting system and a contact closure keypad (not supplied)
  • For use in HomeWorks® QS systems and QS standalone applications


SPECIFICATIONS

Input Power Operating Voltage: 24 to 36 VDC 20mA
Low Voltage SELV / PELV / NEC® Class 2 wiring provides power, derived from QS link. Consumes one Power Draw Unit (PDU)
Environment Ambient operating temperature: 0°C to 40°C / 32°F to 104°F 
Relative Humidity less than 90%, non-condensing.
Indoor use only.
Ambient Operating Temperature 0°C / 32°F  to  40°C / 104°F
Relative Humidity Less than 90%, non condensing
Application For indoor use only
Terminals Each terminal accepts up to two 1.0mm2 (18 AWG) wires, one twisted shielded pair 0.5 mm2 (22 AWG) wire or one 4.0mm2 (12 AWG) wire typical
Contact Closure Input Types The QSE-CI-WCI (WCI) is compatible with both momentary and maintained contact closure inputs (CCIs)

Contact closure keypad must have a low voltage, dry contact closure rating

CCIs must have an on-state saturation voltage less than 1V at 1mA and an off-state leakage current of less than 100uA

The signal pulse for the CCI must be greater than 40ms

Please NoteThe WCI is not designed or rated to work with line/ mains voltage switches – will result in premature failure

Regulatory Approval CE marked
Complies with IEC standards 60669-2-1 and 50428:2005
Recommended Wall Box Dimensions When Installing Unit Depth: 60mm / 2.4” 
Width: 60mm / 2.4”
Dimensions Height: 47mm / 1.85”
Width: 52mm / 2.05”
Depth: 21mm / 0.83”
Diameter: 60mm / 2.4”