LUT-QSE-CI-WCI
The QSE-CI-WCI from Lutron is a control interface for use with HomeWorks QS systems and QS standalone applications. The QSE-CI-WCI integrates a contact closure keypad with a Lutron lighting control system.
The QSE-CI-WCI from Lutron is a control interface for use with HomeWorks QS systems and QS standalone applications. It integrates a contact closure keypad with a Lutron lighting control system. The WCI provides up to eight contact closure inputs (CCIs), which accept maintained or momentary signals.
This CCIs are programmable through the HomeWorks QS system setup software, which means the CCI can be set up to simulate existing Lutron® keypad functionality or custom configured to meet project specific requirements
For QS standalone applications, the CCIs are programmable using the button, DIP switch and LEDs on the WCI.
FEATURES
SPECIFICATIONS
Input Power | Operating Voltage: 24 to 36 VDC 20mA Low Voltage SELV / PELV / NEC® Class 2 wiring provides power, derived from QS link. Consumes one Power Draw Unit (PDU) |
Environment | Ambient operating temperature: 0°C to 40°C / 32°F to 104°F Relative Humidity less than 90%, non-condensing. Indoor use only. |
Ambient Operating Temperature | 0°C / 32°F to 40°C / 104°F |
Relative Humidity | Less than 90%, non condensing |
Application | For indoor use only |
Terminals | Each terminal accepts up to two 1.0mm2 (18 AWG) wires, one twisted shielded pair 0.5 mm2 (22 AWG) wire or one 4.0mm2 (12 AWG) wire typical |
Contact Closure Input Types | The QSE-CI-WCI (WCI) is compatible with both momentary and maintained contact closure inputs (CCIs)
Contact closure keypad must have a low voltage, dry contact closure rating CCIs must have an on-state saturation voltage less than 1V at 1mA and an off-state leakage current of less than 100uA The signal pulse for the CCI must be greater than 40ms Please Note: The WCI is not designed or rated to work with line/ mains voltage switches – will result in premature failure |
Regulatory Approval | CE marked Complies with IEC standards 60669-2-1 and 50428:2005 |
Recommended Wall Box Dimensions When Installing Unit | Depth: 60mm / 2.4” Width: 60mm / 2.4” |
Dimensions | Height: 47mm / 1.85” Width: 52mm / 2.05” Depth: 21mm / 0.83” Diameter: 60mm / 2.4” |
We use cookies to improve your experience on our site. By continuing to browse our site, you agree to the use of cookies. For more information, please see our privacy policy.